Heatcraft Beacon II Error and Alarm Codes

Error, alarm and light codes explained

Home › Commercial Refrigeration Guide › Refrigeration Error Codes › Heatcraft Beacon II Error and Alarm Codes

Updated November 19, 2026

Quick answer

Heatcraft Beacon II walk-in boards show A-codes for alarms and E-codes for errors. A1 is high box temperature, A2 low box temperature, A3 a start-up failure and A4 an input fault. E1 to E5 are sensor faults, E6 is low superheat, E7 is a compressor shutdown on a safety switch, and E9 is a wiring error between evaporators. On E7 the system retries four times, then locks out until it is cycled through Service Mode.

Which systems this page covers

Beacon II is Heatcraft's electronic control for walk-in cooler and freezer refrigeration systems, sold under Heatcraft brands such as Bohn, Larkin, Chandler and Climate Control. The board sits in the evaporator (unit cooler) inside the walk-in and shows codes on a red three-digit LED display. This page uses Heatcraft's Beacon II Refrigeration Systems Installation and Operation Manual, H-IM-79G (June 2020, Part No. 25001401).

Heatcraft publishes that manual as a free PDF: download the Beacon II manual (H-IM-79G). The display and code lists are on pages 10 and 14 to 18, and the troubleshooting guide is on pages 25 to 28.

Heatcraft's newer IntelliGen controller and the Beacon II Smart Controller (a separate LCD panel with codes like *BOXHI) use different displays. They are not covered here.

Normal Beacon II display codes (not errors)

Most of what the display shows is not a fault. While it runs, the board alternates the box temperature with a three-letter mode. On systems with more than one evaporator, the master board shows the box temperature and the mode, and the other (slave) boards show the mode only.

DisplayWhat it means (per Heatcraft)
oFFBox temperature is satisfied and the system is off. The evaporator fans keep running.
CooCooling
PdnPumpdown at the end of a cooling cycle. It lasts until the low pressure switch opens, suction pressure at the evaporator reaches 4 psig, or two minutes pass.
dEFDefrost
drnDraining: the two-minute condensate drain-down after a defrost
dLYDelay: shows while the expansion valve opens on a call for cooling, and after the RESET TIME button is pressed
tStTest mode, started by holding CLEAR/TEST while the system is off. It cycles each output for 10 seconds and stops after 3 sequences.
SErService Mode (see below)
Loc / UnLBoard settings locked / unlocked

Two timers explain most "it is not starting" calls. After power-up or a power failure, the compressor and fans wait out a 4-minute hold-off before starting. Once running, the compressor runs at least 2 minutes, and once off it stays off at least 4 minutes. At power-up, pressing RESET TIME on the board skips the 4-minute hold-off.

Beacon II alarm codes (A-codes)

An alarm closes a set of dry contacts on the board, which can drive a light, buzzer or monitoring system.

CodeMeaning (per Heatcraft)How it clears
A1High box temperature: room temperature stayed above the high alarm setting (ALH) for the alarm time (ALt)Automatically, once box temperature falls back below the alarm setpoint
A2Low box temperature: room temperature stayed below the low alarm setting (ALL) for the alarm timeAutomatically, once box temperature rises above the alarm setpoint
A3System start-up failure: the compressor pumps down and retries after 4 minutes; after 4 failed restarts A3 shows, and the system keeps tryingService Mode or turning off power
A4Input fault: box temperature sensor, suction temperature sensor or pressure transducer open or not installedReplacing the failed sensor or transducer
(power failure)Loss of power to the evaporator also closes the alarm contactsRestoring power

Beacon II error codes (E-codes)

CodeMeaning (per Heatcraft)
E1Room temperature sensor shorted, open or not installed
E2Defrost temperature sensor shorted, open or not installed
E3Suction temperature sensor shorted, open or not installed
E4Suction pressure transducer shorted, open or not installed
E5Outdoor temperature sensor shorted
E6Low superheat during cooling
E7Compressor shut down: high or low pressure switch open, or oil pressure switch open
E9Multi-in / multi-out wiring error (systems with more than one evaporator)

At power-up the board checks its sensors. If the suction sensor or room sensor is shorted, open or missing, the system pumps down, shuts off, and will not restart until the fault is cleared or the breaker is reset.

A1: the walk-in is warm

A1 is the alarm owners see most, and it is a symptom, not a cause. With factory settings, A1 means the box stayed above 50°F (air defrost, typically a cooler) or above 5°F (electric defrost, typically a freezer) for 60 minutes. The high alarm does not apply during defrost. A technician may have changed these settings (ALH and ALt).

Before calling, check the things that warm a box without any equipment failure: a door left open or not sealing, a torn gasket, a heavy load of warm product, or a recent defrost. Then check the evaporator inside the box: is the coil a solid block of ice, and are the fans turning? If the coil is iced over or the fans are stopped, call for service. Our checklist for a walk-in cooler that is not cooling covers the other owner checks.

While you wait, protect the food. Move product that must stay at 41°F or below to another cooler, and log temperatures. Our guide to food safety when refrigeration fails covers the time rules.

E6: low superheat during cooling

Heatcraft's troubleshooting guide defines the E6 trigger as superheat at 0°F for 2 minutes during cooling. Low superheat means liquid refrigerant may be reaching the compressor, which can damage it.

One exception is normal. At first start-up, Heatcraft says the system may cycle off at 2 minutes, show a low superheat error and restart itself, several times, while the electronic expansion valve finds its setting. The manual says not to shut the system off during that period.

Outside start-up, the guide checks, in order: the refrigerant type programmed on the board, ice on the coil (defrost the coil and check defrost settings, the defrost sensor and heater amps), the expansion valve step position, whether the valve closes on pumpdown, whether the compressor runs, and the accuracy of the suction sensor and pressure transducer. Only the ice check (see walk-in freezer ice buildup) is something an owner can see; everything else is technician work with gauges.

E7 error code: compressor shut down by a safety switch

E7 means a safety stopped the compressor: the high or low pressure switch opened, or the oil pressure switch opened. Heatcraft's E7 troubleshooting also covers a compressor protection module, a phase loss monitor and a demand cooling device on units that have them.

How E7 retries and clears

On a high pressure, low pressure or oil pressure cutout, the system pumps down, cycles off and tries again after the 4-minute hold-off. After the fourth try, the alarm contacts close and the code stays on the display. Heatcraft says to clear it by cycling the system through Service Mode after the cause is corrected.

  1. Have the cause found and fixed first. Clearing E7 without a repair just starts the four tries again.
  2. Close the SERVICE switch at the condensing unit. The system pumps down and the board shows SEr.
  3. Return the switch to NORMAL so the system can restart.

On the board itself, pressing FORCE SERVICE twice also pumps the system down, and CLEAR restarts it.

What usually trips it

High pressure on an outdoor condensing unit often comes from a dirty condenser coil or a failed condenser fan, especially on hot days. Heatcraft's list also includes overcharge, air in the system and faulty head pressure or fan cycling controls. Low pressure can come from low refrigerant charge, an iced-over evaporator, a stuck expansion valve or a wrong refrigerant setting on the board.

Look at the condensing unit: is the coil matted with dust or debris, and is the fan turning? Do not reset pressure switches repeatedly. A switch that keeps tripping is protecting the compressor. Book walk-in cooler repair or walk-in freezer repair instead of clearing it again.

888, a blank display, and dLY then oFF

These are power and wiring symptoms rather than numbered codes. The board runs on 24 volts AC from a transformer in the evaporator, and Heatcraft says it may shut down if that supply falls below 18 volts.

What you seeWhat Heatcraft says it points to
888 at power-upPower to the board is below 18 V. Checks: board ground screws, voltage to and from the evaporator transformer, voltage at the board.
888 while buttons are heldNormal. It appears when a technician holds ENTER and CLEAR/TEST to re-initialize a board (then EE?).
nchThe board did not initialize; the initialization steps have to be repeated
Display not litNo power: the disconnect, fuses and breakers, then the transformer and wiring
dLY then oFF, no error shownLow voltage (it can drop too fast to show 888), a short in the wiring from the board to the condensing unit, or a bad compressor contactor coil
Coo but the compressor will not runCompressor internal overload (wait for it to reset), then contactor coil voltage and the contactor itself

An owner can check the breaker and disconnect. Transformer, voltage and contactor checks are electrical work for a technician.

E9: communication wiring between evaporators

E9 only appears on systems with more than one evaporator, and only after the boards first connected successfully. The boards talk in a loop: multi-out on one board to multi-in on the next, and back to the master. Heatcraft lists two causes: crossed wiring (multi-out not wired to multi-in) and broken wiring. Which boards show E9 depends on where the break is, which helps a technician find it.

Service Mode and SEr

Each condensing unit has a SERVICE switch. Closing it pumps the system down and shuts it off, and the board displays SEr. The evaporator fans and heaters also turn off. The system will not restart until the switch is returned to NORMAL. Pressing FORCE SERVICE twice on the board does the same, and CLEAR restarts it. If you see SEr and no one is working on the system, someone may have left the switch closed.

Beacon II factory default settings

When a box will not hold temperature, a changed setting is one of the things a technician checks. These are Heatcraft's defaults for the current (blue, 29310103) board. The older green board (29310101) differs in two places: R-22 on air defrost systems and an 8°F superheat setting.

SettingCodeAir defrost (cooler)Electric defrost (freezer)
Box temperaturebot35°F-10°F
RefrigerantrEFR-404AR-404A
SuperheatSUP7°F7°F
Defrosts per daydFn24
Defrost end temperaturedFt45°F60°F
Defrost fail-safe timedFF40 min30 min
High alarm temperatureALH50°F5°F
Low alarm temperatureALL30°F-15°F
Alarm timeALt60 min60 min

The board can be locked so settings cannot be changed; the display then shows Loc. If yours is not locked, leave settings to the technician, because a wrong refrigerant or superheat value can itself cause E6 or E7.

When to call a technician

Call a technician for A3, A4, any E-code, 888 at power-up, or A1 that does not clear within an hour once the door is closed and the box is not overloaded. E6 and E7 protect the compressor, so get them looked at the same day.

Open 7 days, 8 AM to 5 PM, with emergency service until 9 PM. CA Lic. #776244.

Call 1-800-266-5243Request service online

Frequently asked questions

How do I clear an E7 code on a Beacon II?

Heatcraft says to cycle the system through Service Mode after the cause is corrected: close the SERVICE switch at the condensing unit, then return it to NORMAL. Before the code shows, the system has already retried four times after 4-minute hold-offs, so the fault is real.

What does A1 mean on a Heatcraft walk-in?

A1 is a high box temperature alarm: the walk-in stayed above its high alarm setting for the programmed alarm time (factory settings: 50°F for a cooler or 5°F for a freezer, for 60 minutes). It clears by itself once the temperature comes back down.

What is E6 on a Beacon II?

E6 is low superheat during cooling, 0°F for 2 minutes. At first start-up it can appear and clear on its own a few times. Otherwise it can mean an iced coil, a wrong refrigerant setting, or an expansion valve or sensor problem, and it needs a technician.

What does 888 mean on a Beacon II display?

If 888 shows at power-up, the board is getting less than 18 volts, so the transformer and wiring need checking. 888 also appears briefly, and normally, when a technician re-initializes the board.

Why does my walk-in controller say SEr?

SEr means the system is in Service Mode, usually because the SERVICE switch at the condensing unit is closed. The system stays off until the switch returns to NORMAL.

How do I clear an A3 alarm?

Heatcraft says placing the system in Service Mode or turning off power clears A3. Because A3 means the system failed to start four times, the cause still needs to be found.

Sources