Quick answer
In 2026, new walk-in condensing units face a 1,400 GWP refrigerant limit from 27 Jul 2026 and 150 or 300 GWP from 1 Jan 2032; new self-contained reach-ins must be under 150 GWP since 2025, and new self-contained ice machines since 2026. DOE's 2024 and 2025 efficiency rules for walk-ins and reach-ins were cancelled by Congress. Repairs to existing systems are not restricted.
The federal and California refrigerant dates from 2025 to 2033 that matter to restaurants and stores, each quoted from the rule text, are in our California refrigerant rules timeline.
The short version for owners
- Your existing equipment can still be repaired. EPA states that components used to repair existing systems are not subject to the refrigerant restrictions.
- New equipment is changing. New self-contained units (reach-ins, prep tables, merchandisers, smaller ice machines) now ship with low-GWP refrigerants, usually R-290.
- Walk-in condensing units got more time. EPA's 2026 reconsideration rule replaced the original 1 Jan 2026 deadline with an interim 1,400 GWP limit from 27 Jul 2026 and a stricter limit from 1 Jan 2032.
- The newest DOE efficiency rules are gone. Pages quoting 2027, 2028 or 2029 DOE compliance dates for walk-ins or reach-ins are out of date.
- Leaks now carry paperwork. Since 1 Jan 2026, HFC systems with 15 lb or more of refrigerant fall under EPA leak-repair rules.
Refrigerant limits for new equipment (EPA Technology Transitions)
EPA restricts high-GWP HFC refrigerants in new equipment by sector. The dates below are from EPA's sector table. For self-contained products the date applies to manufacture and import; for systems it applies to installation.
| Equipment | Limit | Applies from |
|---|---|---|
| Self-contained retail units (reach-ins, prep tables, merchandisers) | 150 GWP | 1 Jan 2025 |
| Self-contained ice machines, batch up to 1,000 lb/24 hr or continuous up to 1,200 lb/24 hr | 150 GWP | 1 Jan 2026 |
| Larger self-contained ice machines | Listed substances prohibited | 1 Jan 2027 |
| Remote ice machines | Listed substances prohibited | 1 Jan 2027 |
| Retail food remote condensing units (most walk-ins) | 1,400 GWP, then 150 (200 lb+ charge) or 300 (under 200 lb) | 27 Jul 2026, then 1 Jan 2032 |
| Cold storage warehouses | 700 GWP, then 150 or 300 | 27 Jul 2026, then 1 Jan 2032 |
| Supermarket systems | 1,400 GWP, then 150 or 300 | 1 Jan 2027, then 1 Jan 2032 |
For reference, R-404A has a GWP of about 3,900, so it cannot be used in a newly installed walk-in condensing unit after 27 Jul 2026. Common replacements such as R-448A and R-449A sit under 1,400.
DOE efficiency rules: what was cancelled
DOE published new efficiency standards for walk-in coolers and freezers on 23 Dec 2024 and for commercial refrigerators and freezers on 21 Jan 2025. Congress disapproved both under the Congressional Review Act; the joint resolutions were signed on 9 May 2025 and DOE withdrew both rules effective 20 May 2025. The withdrawal notices state the rules have no force or effect.
The long-standing walk-in design requirements from the Energy Independence and Security Act of 2007 still apply to walk-ins made since 2009, including automatic door closers, strip curtains or spring-hinged doors, and minimum insulation levels (R-25 for cooler walls, ceilings and doors, R-32 for freezer walls, ceilings and doors, R-28 for freezer floors).
Leak repair rules since 1 Jan 2026
Under EPA's Emissions Reduction and Reclamation rule, owners of appliances with 15 lb or more of HFC refrigerant must calculate a leak rate each time refrigerant is added. For commercial refrigeration the trigger is a 20% annual leak rate; leaks above it must be found and repaired within 30 days, with verification tests. Refrigerants with a GWP of 53 or less are exempt.
In practice: keep the service records your technician leaves, and expect a leak search rather than a top-off when a large system keeps losing charge.
What this means when you repair or replace
- Repairing an R-404A walk-in: allowed. Refrigerant cost and availability are the real question, which is part of a repair vs replace decision.
- Replacing a walk-in condensing unit after 27 Jul 2026: the new system needs a refrigerant under 1,400 GWP.
- Buying a new reach-in or small ice machine: it will almost certainly use R-290, which is flammable; service needs technicians trained for it.
- California: CARB has its own refrigerant rules for new facilities and large store chains. Ask your contractor which apply to your site before a major remodel.
Changelog
| Date | Change |
|---|---|
| 27 Jul 2026 | EPA reconsideration rule takes effect: interim limits for remote condensing units and cold storage |
| 26 May 2026 | EPA publishes the Technology Transitions reconsideration rule |
| 1 Jan 2026 | 150 GWP limit for new self-contained ice machines; EPA leak-repair rules begin |
| 20 May 2025 | DOE withdraws the Dec 2024 walk-in and Jan 2025 commercial refrigerator rules |
| 9 May 2025 | Joint resolutions disapproving both DOE rules signed |
| 1 Jan 2025 | 150 GWP limit for new self-contained retail refrigeration units |
Next step
How to choose a commercial refrigeration contractor →
The license, certification and record checks to make before you hire anyone for refrigerant work.
When to call a technician
Planning a replacement or a remodel, or told your system needs a refrigerant change? Ask a C-38 contractor to confirm which limits apply to your exact equipment before you buy.
Open 7 days, 8 AM to 5 PM, with emergency service until 9 PM. CA Lic. #776244.
Frequently asked questions
Is R-404A banned?
Not for repairs. EPA says components used to repair existing systems are not restricted. New walk-in condensing units installed from 27 Jul 2026 must use a refrigerant under 1,400 GWP, which rules out R-404A.
Did DOE's 2028 walk-in efficiency rule take effect?
No. Congress disapproved the December 2024 walk-in rule and DOE withdrew it effective 20 May 2025.
What refrigerant do new reach-ins use?
Since 1 Jan 2025, new self-contained retail units must use refrigerants under 150 GWP. Most manufacturers use R-290 (propane).
Do the leak rules apply to my small reach-in?
The EPA leak-repair rules apply to appliances with 15 lb or more of HFC refrigerant. Most reach-ins hold far less.
Related guides
Sources
- EPA: Technology Transitions HFC restrictions by sector
- Federal Register: Technology Transitions reconsideration rule (26 May 2026)
- Federal Register: DOE withdraws walk-in cooler and freezer standards (20 May 2025)
- Federal Register: DOE withdraws commercial refrigerator standards (20 May 2025)
- EPA fact sheet: AIM Act leak repair requirements (Jan 2026)
- 40 CFR 84.106: leak repair
- 10 CFR 431.306: walk-in cooler and freezer requirements